Technical FAQs

Ask a Question

What is the maximum switching current of relay output (R1& R2) for Altivar 32.


Maximum switching current of relay output (R1& R2) for Altivar 32:

R2 on resistive load, 5 A at 30 V DC, cos phi = 1,
R2 on resistive load, 5 A at 250 V AC, cos phi = 1,
R1, R2 on inductive load, 2 A at 30 V DC, cos phi = 0.4,
R1, R2 on inductive load, 2 A at 250 V AC, cos phi = 0.4,
R1 on resistive load, 4 A at 30 V DC, cos phi = 1,
R1 on resistive load, 3 A at 250 V AC, cos phi = 1,