How is a 4-20mA speed reference signal set up on an ATV71/ATV61 and Relay R2A & R2C -R1 & R2

- Relay R1A & R1C:--
On factory default: R1 was already programmed to “[No drive flt] (FLt)”
In this case, when drive is running, relay R1A and R1C will be NC and when fault comes, it will be NO.

Answer:
Yes, it is correct that bydefault R1 is configured for FLt [No drive fault]
Please, find the below contact status for R1 relay operation for its assignment of FLt
Drive is power OFF => R1A-R1C is open , R1B-R1C is closed
Drive is power ON => R1A-R1C is closed, R1B-R1C is open
Drive is in fault condition => R1A-R1C is open, R1B-R1C is closed


- Relay R2A & R2C:--
you need to program R2 to “[Drv running] (rUn)”
In this case, when drive is running, relay R2A and R2C will be NC.
Answer:
Yes, it is correct if you assign R2 to rUn [ Drv running] then R2 is closed when drive is running.

- You can change relay R1 & R2 configuration as per the requirement.
Answer:
Yes, you can change relay R1 & R2 configuration as per the requirement.

-How is a 4-20mA speed reference signal set up on an ATV71/ATV61
Answer:
Go to the CtL- [Command] menu => Fr1 [Ref.1 channel] = AI2 [ Analog Input]
Go to I-O [Inputs / Outputs] menu => AI2- [AI2 configuration] => Enter, AI2t [ AI2 type]= 0A [ Current], CrL2 [AI2 min value]=  4 mA, CrH2 [AI2 max value] = 20.0 mA

Hope, we answered your query.