Welcome to the Schneider Electric Website

Welcome to our website.

You can choose another country to view available products or go to our Global website for company information.

Choose another country or region

    LC1D25P7 Product picture Schneider Electric

    Range: TeSys D

    Contactors

    LC1D25P7

    LC1D25P7 Product picture Schneider Electric
    Range: TeSys D

    Contactors

    LC1D25P7

    TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 25 A - 230 V AC coil

    Show more characteristics >
    Add to My Favorites Remove from My Favorites

    • Main
      range
      TeSys
      product name
      TeSys D
      product or component type
      Contactor
      device short name
      LC1D
      contactor application
      Motor control
      Resistive load
      utilisation category
      AC-4
      AC-3
      AC-1
      poles description
      3P
      pole contact composition
      3 NO
      [Ue] rated operational voltage
      <= 300 V DC for power circuit
      <= 690 V AC 25...400 Hz for power circuit
      [Ie] rated operational current
      25 A (<= 60 °C) at <= 440 V AC AC-3 for power circuit
      40 A (<= 60 °C) at <= 440 V AC AC-1 for power circuit
      motor power kW
      11 kW at 380...400 V AC 50/60 Hz AC-3
      15 kW at 500 V AC 50/60 Hz AC-3
      15 kW at 660...690 V AC 50/60 Hz AC-3
      5.5 kW at 220...230 V AC 50/60 Hz AC-3
      11 kW at 415...440 V AC 50/60 Hz AC-3
      5.5 kW at 400 V AC 50/60 Hz AC-4
      motor power hp
      2 hp at 115 V AC 50/60 Hz for 1 phase motors
      7.5 hp at 200/208 V AC 50/60 Hz for 3 phases motors
      3 hp at 230/240 V AC 50/60 Hz for 1 phase motors
      7.5 hp at 230/240 V AC 50/60 Hz for 3 phases motors
      15 hp at 460/480 V AC 50/60 Hz for 3 phases motors
      20 hp at 575/600 V AC 50/60 Hz for 3 phases motors
      control circuit type
      AC 50/60 Hz
      [Uc] control circuit voltage
      230 V AC 50/60 Hz
      auxiliary contact composition
      1 NO + 1 NC
      [Uimp] rated impulse withstand voltage
      6 kV conforming to IEC 60947
      overvoltage category
      III
      [Ith] conventional free air thermal current
      40 A at <= 60 °C for power circuit
      10 A at <= 60 °C for signalling circuit
      Irms rated making capacity
      450 A at 440 V for power circuit conforming to IEC 60947
      140 A AC for signalling circuit conforming to IEC 60947-5-1
      250 A DC for signalling circuit conforming to IEC 60947-5-1
      rated breaking capacity
      450 A at 440 V for power circuit conforming to IEC 60947
      [Icw] rated short-time withstand current
      120 A <= 40 °C 1 min power circuit
      240 A <= 40 °C 10 s power circuit
      380 A <= 40 °C 1 s power circuit
      50 A <= 40 °C 10 min power circuit
      100 A 1 s signalling circuit
      120 A 500 ms signalling circuit
      140 A 100 ms signalling circuit
      associated fuse rating
      40 A gG at <= 690 V coordination type 2 for power circuit
      63 A gG at <= 690 V coordination type 1 for power circuit
      10 A gG for signalling circuit conforming to IEC 60947-5-1
      average impedance
      2 mOhm at 50 Hz - Ith 40 A for power circuit
      [Ui] rated insulation voltage
      600 V for power circuit certifications CSA
      600 V for power circuit certifications UL
      690 V for power circuit conforming to IEC 60947-4-1
      690 V for signalling circuit conforming to IEC 60947-1
      600 V for signalling circuit certifications CSA
      600 V for signalling circuit certifications UL
      electrical durability
      1.65 Mcycles 25 A AC-3 at Ue <= 440 V
      1.4 Mcycles 40 A AC-1 at Ue <= 440 V
      power dissipation per pole
      3.2 W AC-1
      1.25 W AC-3
      protective cover
      With
      mounting support
      Plate
      Rail
      standards
      CSA C22.2 No 14
      EN 60947-4-1
      EN 60947-5-1
      IEC 60947-4-1
      IEC 60947-5-1
      UL 508
      product certifications
      BV
      UL
      LROS (Lloyds register of shipping)
      GOST
      CSA
      DNV
      CCC
      RINA
      GL
      connections - terminals
      Control circuit : screw clamp terminals 2 cable(s) 1...2.5 mm² - cable stiffness: flexible - with cable end
      Power circuit : screw clamp terminals 1 cable(s) 1.5...10 mm² - cable stiffness: solid - without cable end
      Control circuit : screw clamp terminals 1 cable(s) 1...4 mm² - cable stiffness: flexible - without cable end
      Control circuit : screw clamp terminals 2 cable(s) 1...4 mm² - cable stiffness: flexible - without cable end
      Control circuit : screw clamp terminals 1 cable(s) 1...4 mm² - cable stiffness: flexible - with cable end
      Control circuit : screw clamp terminals 1 cable(s) 1...4 mm² - cable stiffness: solid - without cable end
      Control circuit : screw clamp terminals 2 cable(s) 1...4 mm² - cable stiffness: solid - without cable end
      Power circuit : screw clamp terminals 1 cable(s) 2.5...10 mm² - cable stiffness: flexible - without cable end
      Power circuit : screw clamp terminals 2 cable(s) 2.5...10 mm² - cable stiffness: flexible - without cable end
      Power circuit : screw clamp terminals 1 cable(s) 1...10 mm² - cable stiffness: flexible - with cable end
      Power circuit : screw clamp terminals 2 cable(s) 1.5...6 mm² - cable stiffness: flexible - with cable end
      Power circuit : screw clamp terminals 2 cable(s) 2.5...10 mm² - cable stiffness: solid - without cable end
      tightening torque
      Control circuit : 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
      Control circuit : 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
      Power circuit : 2.5 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
      Power circuit : 2.5 N.m - on screw clamp terminals - with screwdriver Philips No 2
      operating time
      4...19 ms opening
      12...22 ms closing
      safety reliability level
      B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
      B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
      mechanical durability
      15 Mcycles
      operating rate
      3600 cyc/h at <= 60 °C
      Complementary
      coil technology
      Without built-in suppressor module
      control circuit voltage limits
      0.3...0.6 Uc drop-out at 60 °C, AC 50/60 Hz
      0.8...1.1 Uc operational at 60 °C, AC 50 Hz
      0.85...1.1 Uc operational at 60 °C, AC 60 Hz
      inrush power in VA
      70 VA at 20 °C (cos ϕ 0.75) 60 Hz
      70 VA at 20 °C (cos ϕ 0.75) 50 Hz
      hold-in power consumption in VA
      7.5 VA at 20 °C (cos ϕ 0.3) 60 Hz
      7 VA at 20 °C (cos ϕ 0.3) 50 Hz
      heat dissipation
      2...3 W at 50/60 Hz
      auxiliary contacts type
      Type mechanically linked (1 NO + 1 NC) conforming to IEC 60947-5-1
      Type mirror contact (1 NC) conforming to IEC 60947-4-1
      signalling circuit frequency
      25...400 Hz
      minimum switching current
      5 mA for signalling circuit
      minimum switching voltage
      17 V for signalling circuit
      non-overlap time
      1.5 ms on energisation between NC and NO contact
      1.5 ms on de-energisation between NC and NO contact
      insulation resistance
      > 10 MOhm for signalling circuit
      Environment
      IP degree of protection
      IP20 front face conforming to IEC 60529
      protective treatment
      TH conforming to IEC 60068-2-30
      pollution degree
      3
      ambient air temperature for operation
      -5...60 °C
      ambient air temperature for storage
      -60...80 °C
      permissible ambient air temperature around the device
      -40...70 °C at Uc
      operating altitude
      3000 m without derating in temperature
      fire resistance
      850 °C conforming to IEC 60695-2-1
      flame retardance
      V1 conforming to UL 94
      mechanical robustness
      Vibrations contactor open 2 Gn, 5...300 Hz
      Vibrations contactor closed 4 Gn, 5...300 Hz
      Shocks contactor closed 15 Gn for 11 ms
      Shocks contactor open 8 Gn for 11 ms
      height
      85 mm
      width
      45 mm
      depth
      92 mm
      product weight
      0.37 kg
      Offer Sustainability
      Sustainable offer status
      Green Premium product
      RoHS (date code: YYWW)
      Compliant  - since  0627  -  Schneider Electric declaration of conformity Schneider Electric declaration of conformity
      REACh
      Product environmental profile
      Product end of life instructions
      Available End of life manual
      Contractual warranty
      Warranty period
      18 months
    • Documents and Downloads

      Language
      • English
      Catalogue
      Date
      Size
      Add to My Documents
      Date 8/13/18
      Size 102.7 MB
      CAD
      Date
      Size
      Add to My Documents
      CONTACTOR
      Date 3/12/18
      Size 441.6 KB
      Date 3/12/18
      Size 229.9 KB
      Date 3/12/18
      Size 436.5 KB
      Instruction sheet
      Date
      Size
      Add to My Documents
      Declaration of conformity
      Date
      Size
      Add to My Documents
      Date 7/23/18
      Size 296.4 KB
      End of life manual
      Date
      Size
      Add to My Documents
      Date 11/20/17
      Size 168.8 KB
    • Technical FAQs

      No results found.
      Unfortunately, related FAQs are unavailable due to temporary technical issues. Please try again later.
    • Dimensions Drawings

      Dimensions


      (1)
      Including LAD 4BB
      (2)
      Minimum electrical clearance

      LC1

      D25…D38 (3-pole)

      b

      without add-on blocks

      85

      b1

      with LAD 4BB

      98

      with LA4 D●2

      114(1)

      with LA4 DF, DT

      123(1)

      with LA4 DW, DL

      130(1)

      c

      without cover or add-on blocks

      90

      with cover, without add-on blocks

      92

      c1

      with LAD N or C (2 or 4 contacts)

      123

      c2

      with LA6 DK10, LAD 6K10

      135

      c3

      with LAD T, R, S

      143

      with LAD T, R, S and sealing cover

      147

      (1)

      Including LAD 4BB.


    • Connections and Schema

      Wiring



    • Motor Starter BOM

      Our Proposal - Type 1 : Circuit Breaker + Contactor for Motor Power from 9 to 11 kW and 415 VAC

      Motor power

      (kW)

      ICU

      (kA)

      Breaker

      Contactor (*)

      9

      15


      GV2ME21


      LC1D25P7

      11

      15


      GV2ME22


      LC1D25P7

      Non contractual pictures.

      Type 1 coordination requires that in a short-circuit condition, the contactor or starter must not present any danger to personnel or installations and must not be able to resume operation without repair or the replacement of parts.